| Technical data: MHR 1220 | |
|---|---|
| Measuring range | 35-95% relative humidity |
| Measurement accuracy | ±3.0% relative humidity |
| Switching difference at 50% RH | 4% RH |
| Peak voltage | 250V AC |
| Switching capacity, maximum load Resistive load |
5A 250V(service life 50,000 cycles) |
| Inductive load cos = 0.8 | 0.2A 250V AC |
| Inductive load L/R=3ms | 1A-50V DC,0.5A-75V DC |
| Switching capacity, minimum load | 100mA,20V DC/AC |
| Contact type | Change-over contact |
|
|
|
| Radio interference suppression level | N(in compliance with VDE 0875) |
| Permissible ambient temperature | 0-60℃ |
| Mean temperature coefficient | -20% relative humidity/k at 20℃ and 50% relative humidity |
| Permissible air velocity | 15m/sec |
| Half value period Where V= 2m/sec |
1.2min |
| Mounting position | No constraints |
| Connection | Terminals in casing, 3 × 2.5mm2,3極 3 × 2.5mm2 |
| Casing | Plastic UL94 V-0 |
| Mounting | Clip for 35mm DIN rail(EN 50022) |
| Protection type | IP20 (DIN40050) |
| Dimensions | H × W × D 67×50×38 mm |
| Weight | 60g |